Serviceline Industrial Sensors
Phone: 330-486-0001
Fax: 330-405-4710
Serviceline Explosion Protection
Phone: 330-486-0002
Fax: 330-963-5827

Relay output FB6305B200

FB6305B200
  • 4-channel
  • Outputs wired to Ex e terminals
  • Installation in suitable enclosures in Zone 1
  • Module can be exchanged under voltage (hot swap)
  • Positive or negative logic selectable
  • Simulation mode for service operations (forcing)
  • Permanently self-monitoring
  • Output with watchdog

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  FB6305B200

Slots
Occupied slots2
Supply
Connectionbackplane bus
Rated voltage12 V DC , only in connection with the power supplies FB92**
Power dissipation1.05 W
Power consumption1.05 W
Internal bus
Connectionbackplane bus
Interfacemanufacturer-specific bus to standard com unit
Digital output
Number of channels4
Field device interface
ConnectionRelay output
Connectionwire ends 1/9 (white), 2/10 (brown), 3/11 (green), 4/12 (yellow), 5/13 (grey), 6/14 (pink), 7/15 (blue), 8/16 (red)
Relay
Switching voltageDC: 30 V AC: 230 V
Switching current1 A DC / AC resistive load
Switch power30 W , AC: 250 VA
Minimum load1 V 1 A
Electrical life0.1 mio. cycles
Contact MaterialAgPd gold plated
Response time20 ms (depending on bus cycle time)
Watchdogwithin 0.5 s the device goes in safe state, e.g. after loss of communication
Indicators/settings
LED indicationLED green: supply
LED red: communication fault
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1
Low voltage
Directive 2006/95/ECEN 61010-1
Conformity
Electromagnetic compatibilityNE 21
Degree of protectionIEC 60529
Environmental testEN 60068-2-14
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Damaging gasEN 60068-2-42
Relative humidityEN 60068-2-78
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18
Vibration resistancefrequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles
frequency range 5 ... 100 Hz; transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g; 90 minutes at each resonance
Damaging gasdesigned for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Degree of protectionIP20 (module) , a separate housing is required acc. to the system description
Connectionwire ends or shielded cable tail
wiring connection: separately covered Ex e terminals required
Massapprox. 750 g
Dimensions57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch)
Data for application in connection with hazardous areas
EU-type examination certificatePTB 97 ATEX 1074 U
MarkingEx-Hexagon II 2 G Ex d IIC Gb
Galvanic isolation
Output/power supply, internal bussafe electrical isolation acc. to EN 61010-1
Directive conformity
Directive 2014/34/EUEN 60079-0:2009
EN 60079-1:2007
EN 60079-11:2007
EN 60079-26:2007
EN 61241-11:2006
International approvals
Marine approval
Bureau Veritas Marine22449/B0 BV
General information
System informationThe module has to be mounted in appropriate backplanes (FB92**) in Zone 1, 2, or outside hazardous areas. Observe the corresponding EC-type examination certificate.
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210101
ECLASS 11.027210101
ECLASS 10.0.127210101
ECLASS 9.027210101
ECLASS 8.027210101
ECLASS 5.127210120
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: FB6305B200

The device features 4 independent channels.

The device can be used to switch solenoids, sounders, or lamps.

The device can perform general switching operations, such as switching auxiliary power circuits.

The outputs are galvanically isolated from the bus and the power supply.

Datasheet: FB6305B200

DatasheetFile TypeFile Size
Datasheet FB6305B200PDF865 KB
Datenblatt FB6305B200PDF867 KB

Documents: FB6305B200

ManualsFile TypeFile Size
FB Hardware ManualPDF9157 KB
FB-Hardware-HandbuchPDF9182 KB
Instruction manuals
ИнструкцииPDF144 KB
Návod k poużitíPDF137 KB
Instruktions manualPDF136 KB
Instruction manualPDF60 KB
KasutusjuhendPDF133 KB
KäyttöohjePDF0 KB
Manuel d'instructionsPDF78 KB
BetriebsanleitungPDF64 KB
Οδηγίες χρήσηςPDF148 KB
HandleidingPDF0 KB
Instruction manual / BetriebsanleitungPDF136 KB
Használati útmutatóPDF138 KB
Manuale di istruzioniPDF76 KB
Lietošanas pamācībaPDF136 KB
Instrukciju vadovasPDF138 KB
Instrukcja obsługiPDF139 KB
Manual de instruçõesPDF138 KB
Manual de utilizarePDF137 KB
Návod na poużitiePDF137 KB
Navodila za uporaboPDF135 KB
Manual de instruccionesPDF78 KB
ManualPDF133 KB
Application reports
Application Report - Communication Redundancy for Uninterrupted OperationPDF529 KB
Application Report - LB and FB Remote I/O Systems for Digitally Connecting Analog Field DevicesPDF208 KB
Application Report - Space Saving Extension for Existing PlantsPDF300 KB
Application Report - Using Remote I/O Systems for the Efficient Digitalization of PlantsPDF371 KB
Applikationsbericht - Platzsparende Erweiterung für bestehende AnlagenPDF300 KB
Applikationsbericht - Redundanz der Kommunikation für ungestörten BetriebPDF530 KB
Applikationsbericht - Remote-I/O-Systeme Typ LB und FB für digitale Anbindung analoger FeldgerätePDF208 KB
Applikationsbericht - Remote-I/O-Systeme für effiziente AnlagendigitalisierungPDF365 KB
Documents
Functional Safety ManualPDF2422 KB
Handbuch funktionale SicherheitPDF2435 KB